DocumentCode :
2612722
Title :
State tracking in power systems using DFT-Prony´s method
Author :
Dunlap, Sean ; Begovic, Miroslav M.
fYear :
1993
fDate :
3-6 May 1993
Firstpage :
2192
Abstract :
The authors describe an evolutionary step in improving the measurement of instantaneous phase angle, which is of crucial importance for future real-time control applications for transient stability enhancement. Some of the aspects of the phasor calculations based on uniform sampling and discrete Fourier transforms are outlined. Problems associated with such calculations are demonstrated in simulations and improved solutions proposed based on subsequent fitting of the sliding windows of the sampled data with exponential functions, by using Prony´s technique. Improvements are illustrated by simulation results
Keywords :
Control systems; Frequency measurement; Phase measurement; Power system control; Power system measurements; Power system stability; Power system transients; Power systems; Protective relaying; Velocity measurement;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Circuits and Systems, 1993., ISCAS '93, 1993 IEEE International Symposium on
Conference_Location :
Chicago, IL
Print_ISBN :
0-7803-1281-3
Type :
conf
DOI :
10.1109/ISCAS.1993.394194
Filename :
394194