Abstract :
Low voltage applications mounted on high voltage towers may pose a safety problem in the low voltage network when a flashover occurs over the high-voltage insulators. To study the effects experimentally, a 150 kV system was made available. On a high voltage tower carrying a cellular phone base station, one phase insulator was shorted to the tower. A current of about 200 A was injected into that phase at a large distance. The authors measured the current distribution and the relevant voltages in the low voltage network. A experimental data agree with EMTP calculations. Appropriate measures to guarantee safety for persons and electronic equipment are discussed
Keywords :
cellular radio; current distribution; earthing; flashover; insulators; poles and towers; power overhead lines; safety; telecommunication power supplies; 150 kV; 200 A; EMTP calculations; GSM systems; cellular phone base station; current distribution; flashover; high voltage towers; high-voltage insulators; phase insulator; safety aspects; Base stations; Cellular phones; Current distribution; Current measurement; Flashover; GSM; Insulation; Low voltage; Poles and towers; Safety;
Conference_Titel :
Transmission and Distribution Construction, Operation and Live-Line Maintenance Proceedings. 2000 IEEE ESMO - 2000 IEEE 9th International Conference on
Conference_Location :
Montreal, Que.
Print_ISBN :
0-7803-6625-5
DOI :
10.1109/TDCLLM.2000.882816