• DocumentCode
    2620921
  • Title

    Introduction to arc flash

  • Author

    Lang, M. ; Neal, T. ; Wilkins, R.

  • Author_Institution
    Ferraz Shawmut, Newburyport
  • fYear
    2007
  • fDate
    10-12 Sept. 2007
  • Firstpage
    179
  • Lastpage
    184
  • Abstract
    Arc flash hazard calculations used to predict the magnitude of the heat hazard are based on tests with open-tip vertical electrodes in enclosures. Arc ratings for PPE are developed using opposing electrodes. Tests with electrode configurations that forced the arc plasma jets outward from the box yielded significantly higher heat energy measurements. When placed within this directional plasma flow, protective flame resistant (FR) fabrics yielded significantly lower arc ratings.
  • Keywords
    arcs (electric); electrodes; energy measurement; fabrics; plasma jets; arc flash hazard calculations; arc plasma jets; directional plasma flow; heat energy measurements; heat hazard; magnitude prediction; open-tip vertical electrodes; protective flame resistant fabrics; Chaos; Conductors; Electrodes; Hazards; Heat transfer; Plasma materials processing; Plasma properties; Plasma temperature; Protection; Testing; ATPV; arc flash hazard; arc rating; current limitation; current-limiting fuses; electric fuse;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Fuses and their Applications, 2007. ICEFA 2007. 8th International Conference on
  • Conference_Location
    Clermont-Ferrand
  • Print_ISBN
    978-2-84516-363-8
  • Type

    conf

  • DOI
    10.1109/ICEFA.2007.4419984
  • Filename
    4419984