High crest factor loads on UPS systems
Author :
McLennan, A.A.
Author_Institution :
Emerson Electr. UK Ltd., Swindon, UK
fYear :
1989
fDate :
15-18 Oct 1989
Abstract :
Some of the problems that can be caused by high crest factor (HCF) in UPSs (uninterruptible power supply systems) are outlined. It is noted that the effect of a high crest factor load on a UPS will depend on the technique used to generate the UPS output voltage. Ways to avoid problems with HCF are discussed, including load balancing, the use of a fully rated neutral conductor, the measurement of voltages at the UPS and the load, the correct rating of the UPS, and the use of a third-harmonic filter
Keywords :
load (electric); uninterruptible power supplies; UPS systems; fully rated neutral conductor; high crest factor loads; load balancing; third-harmonic filter; voltage measurement; Capacitors; Computer industry; Computer peripherals; Current measurement; Power engineering and energy; Probes; Switched-mode power supply; Switches; Uninterruptible power systems; Voltage;