• DocumentCode
    2622681
  • Title

    The effectiveness of fire detection and fire sprinkler systems in the central office environment

  • Author

    Edgar, John A

  • Author_Institution
    Bell Canada, Ottawa, Ont., Canada
  • fYear
    1989
  • fDate
    15-18 Oct 1989
  • Abstract
    The results of fire detector testing carried out in the Bell-Northern Research´s Environmental Test Facility in Ottawa, and the results of fire extinguishment testing carried out in the Factory Mutual Research´s Fire Test Center in Rhode Island, are discussed. The objective of the fire detection tests was to evaluate the performance of several types of fire detection system under the variety of air flow conditions found in the ambient environment of central offices housing electronic switching systems. The fire extinguishment tests confirmed various design parameters related to the fire sprinkler protection of digital telecommunications equipment in support of Bell Canada´s proposed program to equip key central offices with automatic fire sprinkler systems. From the extinguishment point of view, fire sprinklers have been shown to be an effective way of preventing the spread of flame beyond the frame of fire origin
  • Keywords
    electronic switching systems; fires; safety systems; testing; air flow conditions; design parameters; electronic switching systems; fire detection; fire sprinkler; performance; safety systems; testing; Automatic testing; Central office; Detectors; Electronic equipment testing; Electronic switching systems; Fires; Production facilities; Protection; System testing; Test facilities;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 1989. INTELEC '89. Conference Proceedings., Eleventh International
  • Conference_Location
    Florence
  • Type

    conf

  • DOI
    10.1109/INTLEC.1989.88350
  • Filename
    88350