DocumentCode :
2627964
Title :
Analysis of antiresonant voltage transformers application efficiency in high-voltage networks
Author :
Laptev, O.I.
Author_Institution :
High Voltage Dept., Novosibirsk State Tech. Univ., Novosibirsk
fYear :
2008
fDate :
23-29 June 2008
Firstpage :
527
Lastpage :
529
Abstract :
The efficiency of the antiresonant voltage transformer (ARVT) in ferroresonance prevention has been studied. Mathematical models for conventional voltage transformer (CVT) and ARVT are presented. The results obtained for the cases of 500 kV ARVT and CVT behavior, as an example, are given. Stability domains of ferroresonance during disconnection of unloaded bus sections are obtained for both ARVT and CVT 500 kV.
Keywords :
ferroresonance; power transformers; antiresonant voltage transformers application efficiency; ferroresonance prevention; high voltage networks; unloaded bus sections; voltage 500 kV; Capacitance; Equivalent circuits; Ferroresonance; Magnetic flux; Magnetic separation; Mathematical model; RLC circuits; Steel; Transformer cores; Voltage transformers; Ferroresonance; antiresonant; overvoltages; switching; voltage transformer;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Strategic Technologies, 2008. IFOST 2008. Third International Forum on
Conference_Location :
Novosibirsk-Tomsk
Print_ISBN :
978-1-4244-2319-4
Electronic_ISBN :
978-1-4244-2320-0
Type :
conf
DOI :
10.1109/IFOST.2008.4602840
Filename :
4602840
Link To Document :