DocumentCode
2629798
Title
Characteristics of high frequency partial discharge for artificially defected extra high voltage accessories
Author
Lee, Su-Kil ; Lee, Chang-Young ; Baek, Joo-Hum ; Kim, Dong-Wook ; Kim, Chung-Sik
Author_Institution
LG Cable Ltd., Kyeong Buk, South Korea
Volume
2
fYear
2000
fDate
2000
Firstpage
682
Abstract
In this paper, the performance evaluation of PD measurement was performed on the cable joints and terminations. The capacitive sensors using metal foil were installed at the appropriated position of joints and terminations. With high frequency PD measurement, an excellent sensitivity below 10 pC could be achieved on on-site (unshielded long distance) conditions. The high frequency PD measurement technique was proven to be an effective diagnostic method for qualification of EHV cable accessories. With this technique, the reliability of the cable system, especially on cable accessories, can be verified on-site condition
Keywords
capacitive sensors; insulator testing; partial discharge measurement; power cable insulation; power cable testing; EHV cable accessory; artificial defect; cable joint; cable termination; capacitive sensor; high-frequency partial discharge measurement; insulation diagnosis; on-site reliability; Attenuation; Calibration; Capacitance; Capacitive sensors; Dielectric losses; Frequency; Partial discharges; Power cables; Sensor phenomena and characterization; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 2000 Annual Report Conference on
Conference_Location
Victoria, BC
Print_ISBN
0-7803-6413-9
Type
conf
DOI
10.1109/CEIDP.2000.884050
Filename
884050
Link To Document