• DocumentCode
    2632381
  • Title

    Transformer based voltage sag generator to perform LVRT and HVRT tests in the laboratory

  • Author

    Wessels, C. ; Lohde, R. ; Fuchs, F.W.

  • Author_Institution
    Inst. of Power Electron. & Electr. Drives, Christian-Albrechts-Univ. of Kiel, Kiel, Germany
  • fYear
    2010
  • fDate
    6-8 Sept. 2010
  • Abstract
    A transformer based voltage sag generator to test renewable energy systems is presented. Design considerations concerning overvoltages and overcurrents during switching action are addressed. Measurement results of a 30 kW laboratory prototype testing a line side PWM converter and a DFIG are presented. Both measurement results for investigations on the transformer based sag generator at the line side converter and the DFIG show the superb functionality of the sag generator. Voltage dips of variable magnitude, duration time and fault type can be generated to perform certification of LVRT capability. The device is also able to perform HVRT tests.
  • Keywords
    asynchronous generators; overvoltage; power convertors; power supply quality; power transformers; DFIG; HVRT tests; LVRT tests; doubly fed induction generator; line side PWM converter; power 30 kW; renewable energy systems; transformer based voltage sag generator; Converters; Generators; Impedance; Laboratories; Switches; Voltage control; Voltage fluctuations; ≪Grid codes≫; ≪HVRT≫; ≪LVRT≫; ≪Voltage sag generator≫;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics and Motion Control Conference (EPE/PEMC), 2010 14th International
  • Conference_Location
    Ohrid
  • Print_ISBN
    978-1-4244-7856-9
  • Type

    conf

  • DOI
    10.1109/EPEPEMC.2010.5606830
  • Filename
    5606830