DocumentCode :
2633009
Title :
Fault Locator approach for high-impedance grounded or ungrounded distribution systems using synchrophasors
Author :
Patynowski, Daniel ; Cardenas, Jorge ; Menendez, David ; Zhiying Zhang ; Roca, Jose Manuel ; Gardy Germain, Jean ; Yunta Huete, Angel ; Canales, Moises ; Martinez, Alvaro ; Rosendo, Jose Antonio ; Roldan, Juan Manuel ; Montanez, Julio
Author_Institution :
GE Digital Energy, Zamudio, Spain
fYear :
2015
fDate :
March 30 2015-April 2 2015
Firstpage :
302
Lastpage :
310
Abstract :
Fault Locators in general are designed for HV solidly grounded systems because of the importance of fault location detection in the overhead transmission lines. In distribution line fault location there are some developments that are based again on the impedance measurement from one end. Accurate fault location in distribution systems is more difficult to achieve because of the existence of multiple branches and also because system neutral point is usually grounded through the high impedance or is ungrounded. In these conditions, fault current is low and with a high capacitive component.
Keywords :
earthing; electric impedance measurement; fault location; phasor measurement; power distribution faults; power distribution lines; HV solidly grounded system; PDC; RTDS; distribution line fault location; fault locator detection approach; fault resistance; grounding point impedance measurement; high-impedance grounded distribution system; high-impedance ungrounded distribution system; overhead transmission line; phasor data concentrator device; real time digital simulator; single-ended algorithm; synchrophasor; Capacitance; Circuit faults; Fault location; Geographic information systems; Impedance; Impedance measurement; Resistance; Fault Locator; In Service Fault Location; Isolated Grounding; On-Site Fault Location; On-line Fault Location; Phasor Measurements Unit (PMU); Synchrophasors;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2015 68th Annual Conference for
Conference_Location :
College Station, TX
Print_ISBN :
978-1-4799-8721-4
Type :
conf
DOI :
10.1109/CPRE.2015.7102173
Filename :
7102173
Link To Document :
بازگشت