• DocumentCode
    2633297
  • Title

    Breaker pole scatter and its effect on quadrilateral ground distance protection

  • Author

    Ryan, James ; Shrestha, Arun ; Thanh-Xuan Nguyen

  • Author_Institution
    Florida Power & Light Co., FL, USA
  • fYear
    2015
  • fDate
    March 30 2015-April 2 2015
  • Firstpage
    488
  • Lastpage
    497
  • Abstract
    In this paper, the effect of breaker pole scatter on quadrilateral ground distance elements is investigated using a simple two-source power system with two short transmission lines. A case study of an unintended operation of a Zone 1 quadrilateral ground distance element due to the delayed opening of a breaker pole in an actual system is presented. A simple solution based on relay logic is proposed to improve the security of quadrilateral ground distance elements. The effectiveness of the proposed solution is verified by running a real-time test using a Real Time Digital Simulator (RTDS®).
  • Keywords
    circuit breakers; poles and towers; power transmission lines; power transmission protection; real-time systems; RTDS; breaker pole scatter; quadrilateral ground distance elements; quadrilateral ground distance protection; real time digital simulator; real-time test; relay logic; short transmission lines; simple two-source power system; unintended operation; Circuit faults; Fault currents; Impedance; Interrupters; Power transmission lines; Relays; Resistance;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Protective Relay Engineers, 2015 68th Annual Conference for
  • Conference_Location
    College Station, TX
  • Print_ISBN
    978-1-4799-8721-4
  • Type

    conf

  • DOI
    10.1109/CPRE.2015.7102187
  • Filename
    7102187