DocumentCode
2633297
Title
Breaker pole scatter and its effect on quadrilateral ground distance protection
Author
Ryan, James ; Shrestha, Arun ; Thanh-Xuan Nguyen
Author_Institution
Florida Power & Light Co., FL, USA
fYear
2015
fDate
March 30 2015-April 2 2015
Firstpage
488
Lastpage
497
Abstract
In this paper, the effect of breaker pole scatter on quadrilateral ground distance elements is investigated using a simple two-source power system with two short transmission lines. A case study of an unintended operation of a Zone 1 quadrilateral ground distance element due to the delayed opening of a breaker pole in an actual system is presented. A simple solution based on relay logic is proposed to improve the security of quadrilateral ground distance elements. The effectiveness of the proposed solution is verified by running a real-time test using a Real Time Digital Simulator (RTDS®).
Keywords
circuit breakers; poles and towers; power transmission lines; power transmission protection; real-time systems; RTDS; breaker pole scatter; quadrilateral ground distance elements; quadrilateral ground distance protection; real time digital simulator; real-time test; relay logic; short transmission lines; simple two-source power system; unintended operation; Circuit faults; Fault currents; Impedance; Interrupters; Power transmission lines; Relays; Resistance;