DocumentCode
2633968
Title
Eigenvalue tracking for PSS placement
Author
Yeu, Rodney ; Sauer, Pete W.
Author_Institution
Dept. of Electr. & Comput. Eng., Univ. of Illinois at Urbana-Champaign, Urbana, IL, USA
fYear
2009
fDate
4-6 Oct. 2009
Firstpage
1
Lastpage
6
Abstract
This paper presents a new method for determining the site for power system stabilizer (PSS) installation. This method tracks the eigenvalues as they go from the interconnected power system to a decoupled system of single machine infinite buses (SMIB). The site for PSS installation is determined by observing to which machine the unstable eigenvalues from the interconnected system track to the decoupled system. This method is compared to the participation factor (PF) placement method for two different power system cases. The results show that the eigenvalue tracking and the PF placement method determined the same site for PSS installment in most cases. In the cases that they did not determine the same location, the eigenvalue tracking method determined the better site for PSS installment in a majority of cases. For completeness both the sites pointed out by the eigenvalue tracking method and the PF placement method should be investigated for PSS installment.
Keywords
Eigenvalues and eigenfunctions; Interconnected systems; Low voltage; Network topology; Power system dynamics; Power system interconnection; Power system modeling; Power systems; Regulators; USA Councils;
fLanguage
English
Publisher
ieee
Conference_Titel
North American Power Symposium (NAPS), 2009
Conference_Location
Starkville, MS, USA
Print_ISBN
978-1-4244-4428-1
Electronic_ISBN
978-1-4244-4429-8
Type
conf
DOI
10.1109/NAPS.2009.5483993
Filename
5483993
Link To Document