DocumentCode :
2638051
Title :
Analysis of the inter-area low frequency oscillations in large scale power systems
Author :
Xiangyi, Chen ; Chunyan, Li ; Yunli, Wang
Author_Institution :
Power Res. Inst., Sichuan Electr., Chengdu, China
fYear :
2011
fDate :
21-23 June 2011
Firstpage :
1627
Lastpage :
1631
Abstract :
With the development of bulk interconnected power grids, the problem of inter-area low frequency oscillations becomes more and more outstanding. This paper analyzes the characteristics of the inter-area oscillation in interconnected power system, the machines participating in oscillation can be equivalent to a two-machine system according to their respective inertia center. Based on the equivalent two-machine system, the electromagnetic torque coefficients are deduced, and then on this deduction the mechanism of the inter-area oscillation is explained. At last, some influence factors are proposed to analyze the inter-area low oscillation. Simulation shows that the frequency and damping of the inter-area oscillation are in close relations with inertia constant, tie-line power flow and excitation characteristic.
Keywords :
power grids; power system interconnection; bulk interconnected power grids; electromagnetic torque coefficients; equivalent two-machine system; inertia constant; inter-area low frequency oscillations; large scale power systems; tie-line power flow; Damping; Electromagnetics; Generators; Load flow; Oscillators; Torque; damping torque; electromagnetic torque; inertia center; inter-area mode; low frequency oscillaton; power system; quick response excitation system;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial Electronics and Applications (ICIEA), 2011 6th IEEE Conference on
Conference_Location :
Beijing
ISSN :
pending
Print_ISBN :
978-1-4244-8754-7
Electronic_ISBN :
pending
Type :
conf
DOI :
10.1109/ICIEA.2011.5975851
Filename :