DocumentCode
2639118
Title
Effect of varying topologies on the performance of broadband over power line
Author
Chandna, Vinay Kumar ; Zahida, Mir
Author_Institution
Electr. Dept., Jamia Millia Islamia, New Delhi, India
fYear
2010
fDate
19-22 April 2010
Firstpage
1
Lastpage
5
Abstract
Power line channel is an alternative to broadband data communication. However, LV power lines present a very harsh environment for high frequency communication signals. The high frequency signal undergoes attenuation due to line loss and impedance mismatch because of branches and loads. Also, the dynamics of system changes the topology of the network very frequently. In this paper, a typical BPL system has been simulated based on echo model of the power line. The effect of varying topologies on the performance of the BPL system has been investigated using different number of branches, load impedances and line lengths. The simulation shows that with the increase in number of branches, the bit error rate increases and poses very little effect on the bit error rate due to variation of load.
Keywords
Bit error rate; Data communication; Impedance; Low voltage; Mathematical model; Network topology; OFDM; Power line communications; Power system modeling; Wiring; BPL; Bit Error Rate; Digital Communication; OFDM;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exposition, 2010 IEEE PES
Conference_Location
New Orleans, LA, USA
Print_ISBN
978-1-4244-6546-0
Type
conf
DOI
10.1109/TDC.2010.5484366
Filename
5484366
Link To Document