• DocumentCode
    2639311
  • Title

    ComEd´s Elmhurst SVCs: Challenges and opportunities

  • Author

    Edris, A. ; Kirschner, L. ; Escher, R. ; Durbak, D. ; Zhou, G. ; Derra, R. ; Fritzsche, M. ; Engelmann, A. ; Schooley, D. ; Torgerson, D. ; Irwin, G. ; Flueck, A.

  • fYear
    2010
  • fDate
    19-22 April 2010
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Elmhurst Substation is located in Commonwealth Edison´s (ComEd´s) Northeast subzone. To support reliability in that area of the system when synchronous condensers that have been in operation in the region are retired, two identical 300 MVAr Static VAr Compensators (SVCs) will be installed at the Elmhurst Substation. Each SVC consists of three Thyristor Switched Capacitors (TSCs) rated at 75 MVAr (TSC1), 75 MVAr (TSC2), and 150 MVAr (TSC3). This paper provides details of the two 300 MVAr SVCs to be installed and commissioned by SIEMENS at the Elmhurst substation. The paper provides the background of system needs for dynamic reactive power support, the designed structure of the two SVCs, and the control and protection system of the two SVCs. The paper also presents results of engineering simulation studies conducted using PSS®E, EMTDC, and RTDS platforms.
  • Keywords
    Capacitors; Control systems; Induction motors; Load modeling; Reactive power control; Reliability engineering; Static VAr compensators; Substations; Synchronous motors; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2010 IEEE PES
  • Conference_Location
    New Orleans, LA, USA
  • Print_ISBN
    978-1-4244-6546-0
  • Type

    conf

  • DOI
    10.1109/TDC.2010.5484377
  • Filename
    5484377