DocumentCode
2641493
Title
Investigation of frequency domain traveling wave fault location methods
Author
Faybisovich, V. ; Feiginov, M. ; Khoroshev, M.I.
Author_Institution
Transm./Substation Eng. Dept., Southern California Edison Co., Los Angeles, CA, USA
fYear
2010
fDate
19-22 April 2010
Firstpage
1
Lastpage
9
Abstract
This paper describes investigation of frequency domain traveling wave fault location methods and consists from two parts. The first part researches how variation of fault and ground resistivity, location of close faults, length of available record affects accuracy of one-ended and double-ended fault location methods. The second part is devoted to development of the new modification of frequency domain routine - two-stage routine, where fault location information is extracted from initiating (until opening of the circuit breakers) as well as from clearing (from CB opening to elimination of the secondary arc) stages of fault. Field testing of the frequency domain method and analytical study of traveling waves for initiation stage of fault clearing are described.
Keywords
Circuit breakers; Circuit faults; Circuit testing; Fault location; Frequency domain analysis; Protective relaying; Resonance; Resonant frequency; Transmission lines; Voltage; double-stage frequency domain method; extraction of resonance harmonic; frequency domain field test; frequency domain traveling wave fault location; traveling wave analytical study;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exposition, 2010 IEEE PES
Conference_Location
New Orleans, LA, USA
Print_ISBN
978-1-4244-6546-0
Type
conf
DOI
10.1109/TDC.2010.5484571
Filename
5484571