DocumentCode
2642485
Title
DC-DC converter plants and their ability to clear distribution fuses
Author
Giancaterino, James A.
Author_Institution
Reliance Comm/Tec, Lorain, OH, USA
fYear
1994
fDate
30 Oct-3 Nov 1994
Firstpage
315
Lastpage
320
Abstract
Accidental faults in the distribution circuits of DC-DC power converter plants can cause voltage dips below the acceptable operating range of the converter loads. Unlike battery plants, converter plants rely solely upon the power supplies to clear fault protection devices. Since the DC-DC power converters are current limited, their ability to clear faults will be based upon the short burst of current from their output capacitors and the excess current available from the plant. As the technologies have taken the DC-DC power converters to higher and higher operating frequencies, their output capacitance has decreased substantially. In the past, the larger capacitors would provide a higher momentary current when a fault was introduced. In many cases, this is not enough. This paper looks at some of the considerations of converter plants with respect to fault clearing, as well as some practical approaches to resolving this problem. A Lorain 6241 converter plant was tested for its fuse clearing capabilities with and without the additional capacitor bank. The results of this testing are presented
Keywords
DC-DC power convertors; distribution networks; electric fuses; electrical faults; power capacitors; power system measurement; power system protection; DC-DC power converter plants; Lorain 6241; capacitor bank; distribution fuses; excess current; fault clearing; fault protection devices; loads; operating frequencies; output capacitance; power supplies; voltage dips; Batteries; Capacitance; Capacitors; Circuit faults; DC-DC power converters; Frequency conversion; Power supplies; Protection; Testing; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 1994. INTELEC '94., 16th International
Conference_Location
Vancouver, BC
Print_ISBN
0-7803-2034-4
Type
conf
DOI
10.1109/INTLEC.1994.396616
Filename
396616
Link To Document