DocumentCode
2645448
Title
Fuzzy control algorithm for universal active filter
Author
Singh, B.N. ; Chandra, Ambrish ; Al-Haddad, Kamal ; Singh, Bhim
Author_Institution
Dept. of Electr. Eng., Ecole de Technol. Superieure, Montreal, Que., Canada
fYear
1998
fDate
35964
Firstpage
73
Lastpage
80
Abstract
In this paper, a fuzzy algorithm is employed to control a three-phase unified power quality conditioner (UPQC). The UPQC is an active filter (AF) and it compensates the reactive power and harmonics in both the voltage and current caused by nonlinear loads. The UPQC makes use of two back-to-back connected IGBT-based voltage source inverters (VSIs) with a common DC bus. One inverter is connected in series while other is placed in shunt with the nonlinear load. The shunt inverter works as a current source and compensates current harmonics caused by nonlinear loads. The series inverter works as a voltage source and helps in compensating the voltage harmonics caused by nonlinear loads. A diode bridge rectifier feeding an R-L load is considered as a nonlinear current load while a source of voltage harmonics is considered in shunt with the load. With a view to examining the steady state and transient performance of the UPQC, a suitable mathematical model of the system is developed. The capability of the UPQC is demonstrated in the filtering of voltage and current harmonics along with the reactive power compensation of nonlinear loads. Simulated results are given and discussed in detail. Experimental results are also given
Keywords
DC-AC power convertors; compensation; control system analysis; control system synthesis; fuzzy control; harmonic distortion; insulated gate bipolar transistors; invertors; load (electric); power bipolar transistors; power filters; power supply quality; power system control; power system harmonics; reactive power control; IGBT VSI; VAr compensation; control design; control performance; control simulation; current harmonics; fuzzy control algorithm; mathematical model; nonlinear loads; steady-state performance; three-phase unified power quality conditioner; transient performance; universal active filter; voltage harmonics; voltage source inverters; Active filters; Diodes; Fuzzy control; Insulated gate bipolar transistors; Inverters; Power harmonic filters; Power quality; Power system harmonics; Reactive power; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Quality '98
Conference_Location
Hyderabad
Type
conf
DOI
10.1109/PQ.1998.710347
Filename
710347
Link To Document