DocumentCode
2654280
Title
Influence of synchronous generator´s stator core on partial discharge on-line measurement
Author
Bertalanic, Zoran ; Pavlica, Milutin ; Maljkovic, Zlatko
Author_Institution
Energy Inst. Inc., Zagreb, Croatia
fYear
2010
fDate
6-8 Sept. 2010
Firstpage
1
Lastpage
5
Abstract
Paper presents the results of on-line partial discharge (PD) measurements of large hydro-generator´s stator winding. Measurements were performed for different load conditions using temporary installed capacitive couplers and applying high frequency phase resolved method. The results show high PD levels caused by core arcing and its change with rise of core temperature.
Keywords
hydroelectric generators; partial discharge measurement; synchronous generators; core arcing; core temperature; high frequency phase resolved method; large hydrogenerator stator winding; partial discharge online measurement; synchronous generator stator core; temporary installed capacitive couplers; Generators; Partial discharges; Phase measurement; Pulse measurements; Stator windings; Temperature measurement; Windings; insulation testing; partial discharges; synchronous generators;