• DocumentCode
    2656458
  • Title

    Basic study on grounding system for high-voltage direct current power supply system

  • Author

    Tanaka, T. ; Honma, Y. ; Kuramoto, Shu ; Tanaka, T. ; Babasaki, Tadatoshi ; Nozaki, Y.

  • Author_Institution
    NTT Energy & Environ. Syst. Labs., Musashino, Japan
  • fYear
    2009
  • fDate
    18-22 Oct. 2009
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    The relationship between grounding systems and a high-voltage direct current (HVDC, 380-V DC) power supply system is presented. To assess the effect of grounding system configurations, a simple model of the HVDC power supply system was assumed, and two typical grounding models were evaluated. The noise emission level (conductive disturbance) was measured by using a prototype HVDC rectifier. By use of the measurement results and evaluations, the advantages and disadvantages of these grounding systems are discussed.
  • Keywords
    HVDC power convertors; earthing; rectifying circuits; HVDC power supply system; HVDC rectifier; conductive disturbance; grounding system; high-voltage direct current power supply system; noise emission level; voltage 380 V; Conductivity measurement; Current supplies; Grounding; HVDC transmission; Noise level; Noise measurement; Power supplies; Power system modeling; Prototypes; Rectifiers;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2009. INTELEC 2009. 31st International
  • Conference_Location
    Incheon
  • Print_ISBN
    978-1-4244-2490-0
  • Electronic_ISBN
    978-1-4244-2491-7
  • Type

    conf

  • DOI
    10.1109/INTLEC.2009.5351759
  • Filename
    5351759