    Influence of the power factor on the degradation of Ag-W electrical contact circuit-breakers

  • Author

    Furtado, H.C. ; Mocarzel, P.R. ; Silveira, V. L A

  • Author_Institution
    CEPEL-Centro de Pequisas de Energia Eletrica, Rio de Janeiro, Brazil
  • fYear
    1991
  • fDate
    6-9 Oct. 1991
  • Firstpage
    33
  • Lastpage
    37
  • Abstract
    Ag-W contacts were evaluated as to their durability by electrical tests, according the IEC 157-1/73, applying different values of power factor. Such contacts were assembled into 30-A single-pole thermomagnetic circuit breakers. The morphology evolution of the arc affected zone was analyzed after 1000, 3000, and 6000 on/off switching cycles with scanning electron microscopy. Based on these results, the contact performances were compared and the influence of the power factor on the degradation of Ag-W contacts of circuit breakers was established.<>
  • Keywords
    circuit breakers; electrical contacts; power factor; silver; tungsten; Ag-W contacts; IEC 157-1/73; arc affected zone; contact performances; degradation; durability; on/off switching cycles; power factor; scanning electron microscopy; thermomagnetic circuit breakers; Circuit testing; Contacts; Current; Degradation; IEC standards; Reactive power;