• DocumentCode
    2659321
  • Title

    Measurement based fault location in three-terminal overhead line and underground cable

  • Author

    Fulczyk, M. ; Balcerek, P. ; Rosolowski, E. ; Izykowski, J. ; Saha, M.M.

  • Author_Institution
    ABB Corp. Res. Center, Krakow, Poland
  • fYear
    2010
  • fDate
    17-20 Oct. 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    This paper presents a new fault location method for three-terminal composite network consisting of two overhead line sections and a cable. Synchronized measurements of three-phase current from all three ends and three-phase voltage - from the bus, where the fault locator (FL) is installed, are utilized for fault location. The fault location algorithm consists of three subroutines designated for locating faults within the respective line/cable sections and a multi-criteria procedure for selecting the valid subroutine. Generalized model of a fault loop are used for formulating the subroutines. Sample results of ATP-EMTP based evaluation are presented and discussed.
  • Keywords
    electric current measurement; fault location; power overhead lines; underground cables; voltage measurement; ATP-EMTP based evaluation; fault location; fault loop; multicriteria procedure; synchronized measurement; three phase current; three phase voltage; three terminal composite network; three terminal overhead line; underground cable;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2010 Annual Report Conference on
  • Conference_Location
    West Lafayette, IN
  • ISSN
    0084-9162
  • Print_ISBN
    978-1-4244-9468-2
  • Type

    conf

  • DOI
    10.1109/CEIDP.2010.5724005
  • Filename
    5724005