    Dynamics of metallic particle contamination in a gas insulated busduct with SF6 and N2 gas mixtures

  • Author

    Rao, M. Ranga ; Amarnath, J.

  • Author_Institution
    V.R. Siddhartha Eng. Coll., Vijayawada, India
  • fYear
    2010
  • fDate
    17-20 Oct. 2010
  • Firstpage
    1
  • Lastpage
    4
  • Abstract
    It is known that breakdown strength of SF6 is extremely susceptible to non-uniform electric fields and metallic particle contamination, these effects lead to lower the breakdown voltage. Furthermore, from the view point of environmental protection, as SF6 has strong greenhouse effect, the use of SF6 will be strong controlled. Thus, it is needed to develop the alternative dielectric gas or gas mixtures having better insulating characteristics and no greenhouse effect. In this paper particle movement with SF6 and N2 mixtures has been simulated and results have been presented in a single phase isolated conductor GIB. The results have been analyzed and presented. It is observed that 40 percent SF6 and 60 percent N2 gives good results, under this condition the GIS can be operated reliably.
  • Keywords
    SF6 insulation; air pollution control; electric conduits; electric fields; insulator contamination; GIB; N2 gas mixtures; SF6 insulation; dielectric gas; gas insulated busduct; greenhouse effect; isolated conductor; metallic particle contamination; non uniform electric fields; Aluminum; Contamination; Copper; Dielectrics; Mathematical model; Silver; Sulfur hexafluoride;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2010 Annual Report Conference on
  • Conference_Location
    West Lafayette, IN
  • ISSN
    0084-9162
  • Print_ISBN
    978-1-4244-9468-2
  • Type

    conf

  • DOI
    10.1109/CEIDP.2010.5724036
  • Filename
    5724036