• DocumentCode
    2660671
  • Title

    Power factor correction at the MIT-Bates Linear Accelerator Center with pulsed loads of up to 180 MW peak (2.7 MW average)

  • Author

    Averill, R. ; Hatch, K. ; Sibley, C. ; Gross, R.

  • Author_Institution
    Bates Linear Accel. Center, MIT, MA, USA
  • Volume
    3
  • fYear
    1997
  • fDate
    12-16 May 1997
  • Firstpage
    3743
  • Abstract
    Power demand charges to MIT-Bates are based on a fixed rate times the greater of kWatt or 0.9 (kVolt A) called for in a 15 minute period within a billing cycle. There have been a number of months in a year when the power factor (PF) was less than 0.9 lagging, resulting in the increase in the demand charges to MIT by the Middleton Municipal Electric Department (MMED). A study resulted in a decision to correct the PF to >0.9 in order to minimize the demand charges. This action would save about $3500 per month in demand charges. Other benefits would also be realized by MIT-Bates and MMED, depending on the installation location. Information obtained on operational AC power requirements for the pulsed loads was obtained by measuring current and voltages at the 480 V inputs to the pulsed loads and at the incoming 22,900 V line input to the facility. A review of the harmonics generated in the voltage and current waveforms at both voltage levels for several operating levels allowed completion of an engineering analysis, which resulted in the selection of a 1200 kVAR switchable capacitor bank to be installed in a wye connection at the 22,900 V incoming line point just after the metering equipment. This paper describes the results of the harmonic studies of the AC power, the pulsed loads required as measured at 480 V, and the resultant overall harmonics generated at the 22,999 V level by the pulsed loads when combined with the other normal AC loads at the Laboratory
  • Keywords
    accelerator RF systems; capacitor switching; electron accelerators; linear accelerators; power factor correction; pulsed power supplies; 1200 kVAr; 180 MW; 2.7 MW; 22900 V; 480 V; MIT-Bates Linear Accelerator Center; current waveforms; harmonics; operational AC power requirements; power demand charges; power factor correction; pulsed loads; switchable capacitor bank; voltage waveforms; wye connection; Current measurement; Linear accelerators; Power demand; Power engineering and energy; Power factor correction; Power measurement; Power system harmonics; Pulse measurements; Reactive power; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Particle Accelerator Conference, 1997. Proceedings of the 1997
  • Conference_Location
    Vancouver, BC
  • Print_ISBN
    0-7803-4376-X
  • Type

    conf

  • DOI
    10.1109/PAC.1997.753404
  • Filename
    753404