The assessment of oil-paper insulation condition based on frequency response method
Author
Liu, Jun ; Wu, Guang-ning ; Lv, Wei ; Zhou, Li-jun ; Min, Ying-jie
Author_Institution
Sch. of Electr. Eng., Southwest Jiaotong Univ., Chengdu, China
fYear
2010
fDate
17-20 Oct. 2010
Firstpage
1
Lastpage
4
Abstract
For analysis of the status of oil-paper insulation, the dielectric response method was used to model oil-paper insulation system. Then the dielectric spectroscopy of oil-paper insulation system was tested. And the influence of oil gap on the test results of oil-paper insulation response was discussed. The results showed that the dielectric response method can effectively assess the status of oil-paper insulation, and the influence of oil gap on the test results is less than 10%.
Keywords
insulation; dielectric response method; dielectric spectroscopy; frequency response method; oil gap; oil-paper insulation condition; oil-paper insulation response; oil-paper insulation system; Dielectric measurements; Dielectrics; Frequency response; Oil insulation; Petroleum; Power transformer insulation;