  • Abstract
    Emitter turn-off (ETO) thyristor based static synchronous compensator (STATCOM) is one of the promising flexible AC transmission system (FACTS) technologies, and it is gaining more popularity in utility grids. A 4.5 MVA ETO based STATCOM failed two ETO devices as over-voltage protection triggered AC connector and disconnected the STATCOM from AC grid supply. This paper presents the investigation of ETO failure reasons. The investigation found that dead time of switching signals is very critical for ETO applications. Protection methods for high power ETO applications are proposed based on failure investigation. Experiments verified the proposed protection method
  • Keywords
    failure analysis; flexible AC transmission systems; overvoltage protection; power grids; static VAr compensators; thyristor applications; STATCOM ETO failure analysis; emitter turn-off thyristor; flexible AC transmission system; over-voltage protection; static synchronous compensator; utility grids; Automatic voltage control; Failure analysis; ETO device; STATCOM; failure analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics and Motion Control Conference, 2006. IPEMC 2006. CES/IEEE 5th International
  • Conference_Location
    Shanghai
  • Print_ISBN
    1-4244-0448-7
  • Type

    conf

  • DOI
    10.1109/IPEMC.2006.4778238
  • Filename
    4778238