DocumentCode
2665504
Title
STATCOM ETO Failure Analysis
Author
Du, Zhong ; Chen, Bin ; Han, Chong ; Yang, Zhaoning ; Song, Wenchao ; Bhattacharya, Subhashish ; Huang, Alex Q.
Author_Institution
Dept. of Electr. & Comput. Eng., North Carolina State Univ., Raleigh, NC
Volume
3
fYear
2006
fDate
14-16 Aug. 2006
Firstpage
1
Lastpage
4
Abstract
Emitter turn-off (ETO) thyristor based static synchronous compensator (STATCOM) is one of the promising flexible AC transmission system (FACTS) technologies, and it is gaining more popularity in utility grids. A 4.5 MVA ETO based STATCOM failed two ETO devices as over-voltage protection triggered AC connector and disconnected the STATCOM from AC grid supply. This paper presents the investigation of ETO failure reasons. The investigation found that dead time of switching signals is very critical for ETO applications. Protection methods for high power ETO applications are proposed based on failure investigation. Experiments verified the proposed protection method
Keywords
failure analysis; flexible AC transmission systems; overvoltage protection; power grids; static VAr compensators; thyristor applications; STATCOM ETO failure analysis; emitter turn-off thyristor; flexible AC transmission system; over-voltage protection; static synchronous compensator; utility grids; Automatic voltage control; Failure analysis; ETO device; STATCOM; failure analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Motion Control Conference, 2006. IPEMC 2006. CES/IEEE 5th International
Conference_Location
Shanghai
Print_ISBN
1-4244-0448-7
Type
conf
DOI
10.1109/IPEMC.2006.4778238
Filename
4778238
Link To Document