DocumentCode :
2672606
Title :
Lightning characterization for flashover rate calculation of overhead transmission lines
Author :
Martinez, Juan A. ; Castro-Aranda, Ferley
Author_Institution :
Dept. d´´Enginyeria Electr., Univ. Politecnica de Catalunya, Barcelona
fYear :
0
fDate :
0-0 0
Abstract :
Lightning characterization for engineering applications is not easy: a flash can be either of negative or positive polarity; negative flashes can consist of several strokes; the waveform and the parameters of the first and the subsequent strokes are very different from each other. This paper is aimed at exploring the influence that a complete characterization of a lightning flash will have on the flashover rate of a transmission line using a Monte Carlo procedure that has been implemented in an electromagnetic transients program
Keywords :
EMTP; Monte Carlo methods; flashover; lightning; power overhead lines; Monte Carlo procedure; electromagnetic transients program; flashover rate calculation; lightning characterization; negative polarity; overhead transmission lines; positive polarity; Conductors; EMTP; Flashover; Lightning; Monte Carlo methods; Power system modeling; Power system transients; Power transmission lines; Surges; Transmission lines; Modeling; Monte Carlo Method; Overvoltages; Power System Lightning Effects; Sensitivity; Statistics;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society General Meeting, 2006. IEEE
Conference_Location :
Montreal, Que.
Print_ISBN :
1-4244-0493-2
Type :
conf
DOI :
10.1109/PES.2006.1708913
Filename :
1708913
Link To Document :
بازگشت