    This paper proposes a novel resonance suppression scheme for a single-phase grid inverter with the LLCL filters. In the structure of the LLCL filters, a small inductor is connected in series with the capacitor in the conventional LCL filters to make zero impedance at the switching frequency, by which the grid-side inductor filter can be reduced remarkably. However, since the resonance phenomenon is a critical issue in this case, a new control method using the proportional and resonant (PR) controllers is proposed to damp out the resonance. The simulation results have verified the effectiveness of the proposed control algorithm for a single-phase grid inverter.
  • Keywords
    circuit resonance; damping; invertors; power filters; proportional control; LLCL filter; PR controller; capacitor; grid-side inductor filter; proportional and resonant controller; resonance damping; resonance suppression scheme; single-phase grid inverter; switching frequency; zero impedance; Active damping; LLCL filters; PR control; Single-phase grid inverterl;