DocumentCode
2672856
Title
Study on Fast Control Algorithm Based on Integrative Sensitivity Analysis
Author
Zhang Baohui ; Cheng Linyan ; Klimek, Andrew ; Bo, Zhi Qian ; Hao Zhiguo ; Li Peng
Author_Institution
Sch. of Electr. Eng., Xian Jiaotong Univ. Xian, Xian, China
fYear
2009
fDate
8-12 Nov. 2009
Firstpage
1
Lastpage
4
Abstract
If the trip of overload branch may cause cascading tripping in corresponding section, emergency overload control should be executed to ensure the security of the transmission section and maintain its integrality and transmission capacity. A series of improvements against the conventional sensitivity algorithm are proposed, which include the advance of the integrative sensitivity, the use of equal and opposite quantities in pairs analysis method, and the introduction of heuristic rules. The choice of control node and its quantity ensures that the power flow of overload branch won´t arise and normal branch won´t overload, so the control strategy can availably and quickly eliminate overload. The rapidity and validity of proposed algorithm is verified by a lot of calculation results of a certain real system.
Keywords
load flow control; power transmission control; control node; emergency overload control; fast control algorithm; integrative sensitivity analysis; power flow; transmission capacity; Algorithm design and analysis; Automatic control; Automation; Load flow; Power generation; Protection; Security; Sensitivity analysis; USA Councils; Yarn;
fLanguage
English
Publisher
ieee
Conference_Titel
Intelligent System Applications to Power Systems, 2009. ISAP '09. 15th International Conference on
Conference_Location
Curitiba
Print_ISBN
978-1-4244-5097-8
Electronic_ISBN
978-1-4244-5098-5
Type
conf
DOI
10.1109/ISAP.2009.5352960
Filename
5352960