• DocumentCode
    2672874
  • Title

    Overview of Anti-Islanding Algorithms for PV Systems. Part I: Passive Methods

  • Author

    De Mango, Francesco ; Liserre, Marco ; Aquila, Antonio Dell ; Pigazo, Alberto

  • Author_Institution
    GRTN S.p.A, Rome
  • fYear
    2006
  • fDate
    Aug. 30 2006-Sept. 1 2006
  • Firstpage
    1878
  • Lastpage
    1883
  • Abstract
    This paper offers an overview of the passive methods used for islanding detection. A monitoring PLL has been adopted for the estimation of the voltage amplitude and frequency. Passive inverter resident methods discussed are the over/under voltage (OUV), over/under frequency (OUF), the voltage harmonic monitoring (with a study on the effects of the grid impedance value and of the inverter DC voltage ripple) and the phase monitoring (different from the classical phase jump method). A harmonic synchronization PLL is used to monitor the 3 rd, 5th and 7th harmonics. All the proposed algorithms are validated by simulations and experimental results obtained in accordance with the IEEE Std. 929-2000 procedure
  • Keywords
    invertors; monitoring; phase locked loops; photovoltaic power systems; power system harmonics; PLL monitoring; PV systems; antiislanding algorithms; harmonic synchronization; passive inverter; phase monitoring; voltage harmonic monitoring; Distributed control; Fault detection; Frequency estimation; Inverters; Monitoring; Phase locked loops; Power supplies; Power system protection; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics and Motion Control Conference, 2006. EPE-PEMC 2006. 12th International
  • Conference_Location
    Portoroz
  • Print_ISBN
    1-4244-0121-6
  • Type

    conf

  • DOI
    10.1109/EPEPEMC.2006.4778679
  • Filename
    4778679