DocumentCode :
267632
Title :
Security constrained optimal power flow for HVAC and HVDC grids
Author :
Wiget, Roger ; Iggland, Emil ; Andersson, Goran
Author_Institution :
ETH Zurich, Zurich, Switzerland
fYear :
2014
fDate :
18-22 Aug. 2014
Firstpage :
1
Lastpage :
7
Abstract :
This paper includes security constraints in OPF calculations for combined HVAC and HVDC grids. Two formulations of the problem are considered: a preventive and a corrective formulation. The outages of lines, generators and terminal stations are included. The preventive control method assumes that no control actions are taken after a contingency happens, meaning that all actions must be performed in advance. Linear sensitivity factors are used to calculate the influence of the contingency. Under the corrective control method, control actions can be performed both before and after a contingency, using fast controllable HVDC terminals. The two methods are applied to the IEEE14 and the RTS96 test cases, both expanded with an HVDC grid. The corrective control is computationally more intensive, but, in general, gives more economical results.
Keywords :
HVAC; HVDC power transmission; load flow control; power distribution planning; HVAC grid; HVDC grid; IEEE14 test case; RTS96 test case; linear sensitivity factors; power system planning; preventive control method; security constrained optimal power flow; Generators; HVDC transmission; Linear programming; Load flow; Security; Topology; Voltage control; Generalized Generator Distribution Factors; HVDC; Line outage distribution factors; Optimal Power Flow; Power System Planning; SCOPF;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Systems Computation Conference (PSCC), 2014
Conference_Location :
Wroclaw
Type :
conf
DOI :
10.1109/PSCC.2014.7038444
Filename :
7038444
Link To Document :
بازگشت