Abstract :
The major part of disturbs in electrical systems occurs in transmission lines. These disturbs are in most cases single-phase and transitory and mainly caused by atmospheric electrical discharges. In this paper, the voltage-current cross relation characteristic of the secondary arc was investigated using open air experimental data. With more than 500 artificially generated long electrical arcs, a methodology to calculate the stationary secondary arc conductance and capacitance is presented, alongside with the capacitive and conductive values for several arc currents, which were varied from 15 Arms to 500 Arms.
Keywords :
arcs (electric); power transmission faults; long electrical arcs; secondary arc current range; stationary secondary arc capacitance; stationary secondary arc conductance; transmission lines; voltage-current cross relation characteristic; Capacitance; Circuit faults; Equations; Insulators; Mathematical model; Power system stability; Power transmission lines;