• DocumentCode
    2681937
  • Title

    Protection scheme for a new AC railway traction power system

  • Author

    Sezi, Tevfik ; Menter, Frank E.

  • Author_Institution
    Distribution Autom. Div., Siemens Power Transmission & Distribution, Raleigh, NC, USA
  • Volume
    1
  • fYear
    1999
  • fDate
    11-16 Apr 1999
  • Firstpage
    388
  • Abstract
    The new, 160 mile long Amtrak Northeast Corridor railway electrification project has four supply substations that connect 115 kV utility power to the 55 kV single-phase, AC traction power system. Eighteen autotransformer-paralleling stations are spaced along the route. Each autotransformer connects the overhead catenary to an auxiliary feeder line, with the rails tied to an intermediate point of the autotransformer. Each train draws power from two adjoining autotransformers. The protection scheme includes distance protection for the catenary and feeder lines, transformer protection for the power transformers and autotransformers, plus bus protection and backup protection. The protection scheme uses a specialized type of numerical distance protection relay optimized for railway traction systems. In the event of a fault on the protected part of the line, a trip occurs and the relay calculates the distance to the fault. All the autotransformers within that distance are automatically disconnected, and the relay attempts a reclose. If the reclose is successful, the autotransformers are reconnected
  • Keywords
    autotransformers; power system protection; power system relaying; power transformer protection; railways; relay protection; substations; traction; 115 kV; 160 mile; 55 kV; AC railway traction power system protection scheme; USA; autotransformer; auxiliary feeder line; backup protection; bus protection; distance protection relay; overhead catenary; railway electrification project; relay reclosing; substations; transformer protection; Frequency conversion; Power generation; Power supplies; Power system protection; Power system relaying; Power transformers; Power transmission; Protective relaying; Rail transportation; Railway electrification;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference, 1999 IEEE
  • Conference_Location
    New Orleans, LA
  • Print_ISBN
    0-7803-5515-6
  • Type

    conf

  • DOI
    10.1109/TDC.1999.755383
  • Filename
    755383