DocumentCode
2683175
Title
Simulation and analysis of a major disturbance in Entergy system that resulted in voltage collapse
Author
Kolluri, V.S. ; Mandal, S. ; Powell, Raymon D. ; Vongkhamchanh, Kham
Author_Institution
Entergy Services Inc., New Orleans, LA
fYear
0
fDate
0-0 0
Abstract
In June 2005, severe weather in the Western Region of the Entergy System precipitated forced interruption of three critical lines in the same right-of-way. Loss of these lines led to a fast voltage collapse within the Western region. Within seconds, the generation and other critical lines in the area tripped, and over several minutes Western Region separated from the rest of the system. System studies were performed to replicate the disturbance and understand the cause of the fast voltage collapse. This paper discusses the events that led to collapse, modeling issues related to simulation and the results of the steady state and dynamic analysis
Keywords
power system dynamic stability; power system faults; Entergy ystem disturbance interruption; Western region; dynamic analysis; modeling issues; steady state analysis; voltage collapse; Analytical models; Discrete event simulation; Phasor measurement units; Power transmission lines; Region 3; SCADA systems; Stability analysis; Steady-state; Voltage; Wind; Digital Fault Recorder (DFR); P-V Analysis; Phasor Measurement Unit (PMU); Supervisory Control and Data Acquisition (SCADA); Voltage Collapse; Voltage Stability;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society General Meeting, 2006. IEEE
Conference_Location
Montreal, Que.
Print_ISBN
1-4244-0493-2
Type
conf
DOI
10.1109/PES.2006.1709530
Filename
1709530
Link To Document