DocumentCode :
2684240
Title :
Application of the optimal damper on damping turbine-generator torque vibrations in a HVDC link
Author :
Tsai, Jong-Ian ; Wu, Ron-Chin
Author_Institution :
Dept. of Electron. Eng., Kao Yuan Inst., Kaohsiung
fYear :
0
fDate :
0-0 0
Abstract :
Due to more various power disturbances occurring in a power system involving a HVDC link, the turbine generator shafts and/or blades are more prone to damage than in general HVAC systems. In this paper, a new mechanical damper scheme based on participation factor approach is proposed to damp torsional torque and prolong the life of turbine mechanism. Two types of torsional damping couplings, inertia damping coupling and elastic damping coupling, are adopted and examined. The optimal type and the optimal location of the damping coupling will be identified and installed to the turbine generator shaft section. The simulation results demonstrate that the best damper may not be installed at the location with the most onerous vibrations but provides satisfactory damping performance on shafts and blades following severe power disturbances in a HVDC link
Keywords :
HVDC power transmission; blades; damping; power transmission faults; shafts; torque; turbogenerators; vibrations; HVAC systems; a HVDC link; blades; elastic damping coupling; inertia damping coupling; mechanical damper; optimal damper; power disturbances; torsional damping couplings; torsional torque damping; turbine generator shafts; turbine-generator torque vibrations; vibrations damping; Blades; Damping; HVDC transmission; Power generation; Power systems; Shafts; Shock absorbers; Torque; Turbines; Vibrations; Damper; HVDC; Harmonics; Torsional Vibration; Turbine;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society General Meeting, 2006. IEEE
Conference_Location :
Montreal, Que.
Print_ISBN :
1-4244-0493-2
Type :
conf
DOI :
10.1109/PES.2006.1709587
Filename :
1709587
Link To Document :