Title :
GPS-synchronized harmonic measurements performed on a 400kV transmission network
Author :
Wiechowski, Wojciech ; Lykkegaard, Jan ; Bak-Jensen, Birgitte ; Bak, Claus Leth ; Wasilewski, Jacek
Author_Institution :
Energinet.dk, Fredericia
Abstract :
In this paper, GPS-synchronized harmonic measurements performed on the transmission network of the Danish TSO Energinet.dk are presented. The purpose of the measurements was to verify a computer model of the network. The selected verification method was based on determination of transfer harmonic impedance by switching a series component that contains a shunt branch [1], [2]. Harmonic currents and voltages were simultaneously measured at three 400 kV substations with OMICRON CMC256 units with EnerLyzer function and GPS synchronization units. Time domain "snapshot" measurements of three-phase voltages and currents were synchronously taken, while a power line was switched out and in, and the results were post-processed in Matlab. Harmonic voltages were measured using capacitive taps of the 400 kV/150 kV autotransformer bushings. Harmonic currents were measured as voltage drop on low-inductance resistors inserted in series with the metering equipment. Due to largely unbalanced harmonic currents, the computer network model was verified by a modified verification method, based on injection of measured harmonic currents and comparison of resultant voltage increments. The method requires precise synchronization of the units and sufficient level of harmonic distortion in the network.
Keywords :
Global Positioning System; autotransformers; electric current measurement; harmonic distortion; impedance matrix; power system harmonics; power system measurement; power transmission lines; substations; synchronisation; time-domain analysis; voltage measurement; GPS-synchronized harmonic measurements; Matlab; autotransformer bushings; bus impedance matrix; capacitive taps; harmonic current measurement; harmonic distortion; harmonic voltage measurement; power line; substations; time domain measurements; transmission network; voltage 150 kV; voltage 400 kV; Computer networks; Current measurement; Energy measurement; Global Positioning System; Impedance; Mathematical model; Performance evaluation; Power measurement; Substations; Voltage; bus impedance matrix; global positioning system; harmonic analysis; impedance matrix; impedance measurement; power system harmonics; time domain measurements;
Conference_Titel :
Electrical Power Quality and Utilisation, 2007. EPQU 2007. 9th International Conference on
Conference_Location :
Barcelona
Print_ISBN :
978-84-690-9441-9
Electronic_ISBN :
978-84-690-9441-9
DOI :
10.1109/EPQU.2007.4424111