DocumentCode :
2689807
Title :
A new method to calculate power distribution losses in an environment of high unregistered loads
Author :
Poveda, Mentor
Volume :
2
fYear :
1999
fDate :
11-16 Apr 1999
Firstpage :
609
Abstract :
The paper presents a new method to break down, by subsystem and cause, power distribution losses in electrical systems where the share of nontechnical losses is important. In this type of system the traditional method has given rise to inaccuracies due to high unregistered load. The new method is based on the nature of the losses: resistive losses obtained from the squared ratio between hourly demand and maximum demand, in each subsystem; transformer core losses not related to the demand variations at the substation and at the primary distribution feeders; and nontechnical losses with a demand profile similar to that of the load since they involve unregistered loads. The method uses load profiles registered in today´s generalized electronic meters. The paper demonstrates the differences in calculated losses obtained by the new method compared to the use of the traditional loss factor
Keywords :
distribution networks; load (electric); losses; power transformers; substations; demand profile; electrical power systems; high unregistered loads environment; nontechnical losses; power distribution losses calculation; primary distribution feeders; substation; transformer core losses; Costs; Energy measurement; Erbium; Information processing; Loss measurement; Power distribution; Power measurement; Propagation losses; Substations; Transformer cores;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference, 1999 IEEE
Conference_Location :
New Orleans, LA
Print_ISBN :
0-7803-5515-6
Type :
conf
DOI :
10.1109/TDC.1999.756121
Filename :
756121
Link To Document :
بازگشت