• DocumentCode
    2695286
  • Title

    Single-frame dual-voltage generator, AC and DC output with independent control

  • Author

    Kusko, Alexander

  • Author_Institution
    Exponent Failure Anal. Associates, Natick, MA, USA
  • fYear
    2004
  • fDate
    19-23 Sept. 2004
  • Firstpage
    230
  • Lastpage
    233
  • Abstract
    Numerous examples are evident of the need for a compact electric generator that can provide dual independently controlled AC and DC voltage outputs for such applications as standby service, aircraft and vehicle electrical systems, and other applications. The generator described here utilizes radial air-gap magnetic fields of different pole numbers with dual stator and field windings, which also might be combined. The pole numbers are selected for the magnetic fields to be orthogonal, i.e., noninterfering. The article describes winding patterns, anticipated performance, and trade-offs between a dual-voltage generator and two separate generators.
  • Keywords
    aircraft; electric vehicles; emergency power supply; magnetic fields; standby generators; stators; voltage control; AC voltage; DC voltage; aircraft; anticipated performance; dual stator; field windings; pole; radial air-gap magnetic fields; single-frame dual-voltage generator; standby service; two separate generators; vehicle electrical systems; AC generators; Aerospace control; Air gaps; Aircraft; Control systems; DC generators; Electric vehicles; Magnetic fields; Stators; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2004. INTELEC 2004. 26th Annual International
  • Print_ISBN
    0-7803-8458-X
  • Type

    conf

  • DOI
    10.1109/INTLEC.2004.1401471
  • Filename
    1401471