Abstract
The results of research into the possibility to use coaxial cable lengths for protection of capacitors in large capacitor banks are presented. The pulsed current value permissible for cable in normal operation is estimated in view of the strength of outer conductors under the action of electrodynamic forces. The motion of the outer conductors and cable sheath caused by electrodynamic forces arising in the emergency modes at capacitor breakdown was observed. The experiments revealed that the outer conductors disintegrate in the emergency modes because of overheating, softening and subsequent break of the outer conductors in the points of interlacing and electrical contacts between these conductors. It was found that the polyethylene sheath of the cable provides conditions for arc extinction and current interruption in emergency modes.
Keywords
arcs (electric); capacitor storage; coaxial cables; electric breakdown; arc extinction; capacitor breakdown; capacitor protection; coaxial cable; current interruption; electrodynamic forces; large capacitors banks; polyethylene sheath; protection of capacitors; pulsed current; Cable shielding; Capacitors; Coaxial cables; Conductors; Contacts; Electric breakdown; Electrodynamics; Polyethylene; Protection; Softening;
fLanguage
English
Publisher
ieee
Conference_Titel
Pulsed Power Conference, 2003. Digest of Technical Papers. PPC-2003. 14th IEEE International
Conference_Location
Dallas, TX, USA
Print_ISBN
0-7803-7915-2
Type
conf
DOI
10.1109/PPC.2003.1278026
Filename
1278026
Link To Document