Title :
Leakage current and performance of silicone rubber insulators during salt-storms
Author :
Vlastós, A.E. ; Sörqvist, T.
Author_Institution :
Chalmers Univ. of Technol., Goteborg, Sweden
Abstract :
The leakage current and the performance of silicone rubber insulators during a salt-storm were studied at the Anneberg research station. A relative comparison of leakage current data was made for insulators with leakage distance in accordance with valid specifications and for insulators with shorter leakage distance i.e. higher electric stress. The data show that a high voltage AC or DC insulator, with silicone rubber surface and leakage distance in accordance with valid specifications, maintains low leakage currents under severe salt-storm conditions experienced on the Swedish west coast. However, a silicone rubber insulator with a much shorter leakage distance may show high leakage currents
Keywords :
insulator contamination; leakage currents; silicone rubber; silicone rubber insulators; storms; Anneberg research station; HVAC insulator; HVDC insulator; Swedish west coast; electric stress; leakage current; leakage distance; salt-storms; silicone rubber insulators; Dielectrics and electrical insulation; Insulator testing; Leakage current; Pollution; Rubber; Silicon on insulator technology; Stability; Stress; Transmission lines; Voltage;
Conference_Titel :
Electrical Insulation, 1994., Conference Record of the 1994 IEEE International Symposium on
Conference_Location :
Pittsburgh, PA
Print_ISBN :
0-7803-1942-7
DOI :
10.1109/ELINSL.1994.401401