Title :
Control methods of hybrid active power filters reduced rating of its converter
Author :
Junling, Chen ; Yaohua, Li ; Xinjian, Jiang ; Dongqi, Zhu
Author_Institution :
Inst. of Electr. Eng., Chinese Acad. of Sci., Beijing
fYear :
2008
fDate :
21-24 April 2008
Firstpage :
1
Lastpage :
4
Abstract :
This paper presents three control methods for a hybrid active power filter (HAPF), which is reduced the rating of active converter. Main circuit topology and their principles of the HAPF were discussed in detail. The single-phase equivalent circuits in harmonic domain of the HAPF are also given. Experiment waveforms were gotten from a laboratory prototype, rated at 10 kVA. Experiment results prove the active converter rating accounts for only 4.42% of the HAPF rating while the total harmonic distortion of the source current is reduced to 4.25% from 26.95% with the combined control method, which is better than the other control methods.
Keywords :
active filters; harmonic distortion; network topology; power convertors; power filters; power system control; active converter; apparent power 10 kVA; control methods; hybrid active power filters reduced rating; main circuit topology; total harmonic distortion; Active filters; Circuit topology; Equivalent circuits; Filtering; Laboratories; Power harmonic filters; Power system harmonics; RLC circuits; Resonance; Voltage; control method; fundamental resonance circuit; hybrid active power filter;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Industrial Technology, 2008. ICIT 2008. IEEE International Conference on
Conference_Location :
Chengdu
Print_ISBN :
978-1-4244-1705-6
Electronic_ISBN :
978-1-4244-1706-3
Type :
conf
DOI :
10.1109/ICIT.2008.4608432
Filename :
4608432