• DocumentCode
    270557
  • Title

    Interactions between STATCOM and VSC HVDC in dynamic GB system

  • Author

    Shen, L. ; Barnes, M. ; Milanović, Jovica V.

  • Author_Institution
    Sch. of Electr. & Electron. Eng., Univ. of Manchester, Manchester, UK
  • fYear
    2014
  • fDate
    8-10 April 2014
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper analyses the operation and interaction of a STATCOM and a VSC HVDC link located in close electrical proximity in an AC system, taking into consideration of various controller configurations and operating conditions for both components. It is identified that the dynamic behaviour of one component can be substantially affected by a parametric event in the control of the other component whereas little interaction is shown between the two components for an AC system short circuit event. Results also indicate that the operating point of the DC link can deteriorate the transient performance of both the STATCOM and VSC. The study is performed based on a multi-machine dynamic GB system developed from a real reference load flow case to achieve higher fidelity.
  • Keywords
    HVDC power convertors; short-circuit currents; static VAr compensators; transient analysers; AC system; DC link; STATCOM; VSC HVDC; load flow; multimachine dynamic GB system; short circuit event; transient performance; Control Interactions; Dynamic GB System; STATCOM; VSC HVDC;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Power Electronics, Machines and Drives (PEMD 2014), 7th IET International Conference on
  • Conference_Location
    Manchester
  • Electronic_ISBN
    978-1-84919-815-8
  • Type

    conf

  • DOI
    10.1049/cp.2014.0317
  • Filename
    6836991