• DocumentCode
    2707201
  • Title

    Polarisation spectrum analysis for diagnosis of oil/paper insulation systems

  • Author

    Osvath, Peter ; Zahn, Hans

  • Author_Institution
    TETTEX Instrum. AG, Zurich, Switzerland
  • fYear
    1994
  • fDate
    5-8 Jun 1994
  • Firstpage
    155
  • Lastpage
    161
  • Abstract
    This new method can be described as the diagnosis of the state of an oil/paper insulated high voltage system by polarisation spectrum obtained from the results of recovery voltage measurement. The technique of recovery voltage measurement offers a useful non-intrusive diagnostic procedure for assessing oil-paper condition of transformers. The technique is primarily a comparative tool intended for repeat measurements over a period to indicate trends in insulation degradation. With experience, and taking due account of related factors such as temperature, recovery voltage measurement can also be used to give a quick indication of the health of the insulation system in any oil/paper insulated electrical equipment
  • Keywords
    insulating oils; insulation testing; paper; polarisation; power transformer insulation; power transformer testing; spectral analysis; voltage measurement; insulated high voltage system; insulation degradation; non-intrusive diagnostic procedure; oil/paper insulation systems; polarisation spectrum analysis; recovery voltage measurement; transformers; Aging; Capacitance; Capacitors; Electrodes; Moisture; Oil insulation; Optical polarization; Petroleum; Power transformer insulation; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1994., Conference Record of the 1994 IEEE International Symposium on
  • Conference_Location
    Pittsburgh, PA
  • ISSN
    1089-084X
  • Print_ISBN
    0-7803-1942-7
  • Type

    conf

  • DOI
    10.1109/ELINSL.1994.401445
  • Filename
    401445