Abstract :
In order to adequately assess the condition of field aged XLPE cable it is necessary to select diagnostic test methods which are sensitive to each type of detection. The paper reports the results of a field test program to evaluate the condition of a number of aged XLPE cables operating at 12 kV and 25 kV line-to-line. Promising test methods included time domain reflectometry to detect and locate PD sources as well as other anomalies in the dielectric. These sites may be temporarily enhanced as a result of selected overpotential tests at a moderate level. Subsequent dissection has revealed extensive water trees and incipient failures in the detected locations
Keywords :
XLPE insulation; ageing; failure analysis; power cable insulation; power cable testing; time-domain reflectometry; trees (electrical); 12 kV; 25 kV; diagnostic test methods; dielectric anomalies; field aged XLPE cables; incipient failures; line-to-line voltages; overpotential tests; time domain reflectometry; water trees; Aging; Cable insulation; Current measurement; Dielectric measurements; Leakage current; Partial discharge measurement; Partial discharges; Testing; Trees - insulation; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1994., Conference Record of the 1994 IEEE International Symposium on
Conference_Location :
Pittsburgh, PA
ISSN :
1089-084X
Print_ISBN :
0-7803-1942-7
Type :
conf
DOI :
10.1109/ELINSL.1994.401460
Filename :
401460
Link To Document :
بازگشت