Voltage inversion due to presence of SSSC on adjacent lines and distance relay mal-operation
Author
Jamali, S. ; Kazemi, A. ; Shateri, H.
Author_Institution
Iran Univ. of Sci. & Technol., Tehran
fYear
2008
fDate
21-24 April 2008
Firstpage
1
Lastpage
6
Abstract
This paper discusses the distance relay mal-operation in the presence of static synchronous series compensator (SSSC), one of the series connected Flexible Alternating Current Transmission System (FACTS) device. This is done by presenting the measured impedance at the relaying point in the case of SSSC presence at the near end of the line behind. Measured impedance by distance relay is greatly influenced in the presence of SSSC on the transmission line or even in the case of installation of SSSC on the adjacent lines, near end of the line behind. Distance relay tripping characteristic depends on many factors including the power system structural conditions and the pre-fault loading, the ground fault resistance, and SSSC structural and controlling parameters.
Keywords
electric impedance measurement; flexible AC transmission systems; power transmission lines; power transmission protection; relay protection; static VAr compensators; FACTS device; Flexible Alternating Current Transmission System; SSSC; distance relay mal-operation; impedance measurement; static synchronous series compensator; transmission line; tripping characteristic; voltage inversion; Flexible AC transmission systems; Impedance measurement; Power system faults; Power system measurements; Power system relaying; Power transmission lines; Protective relaying; Relays; Transmission line measurements; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Industrial Technology, 2008. ICIT 2008. IEEE International Conference on
Conference_Location
Chengdu
Print_ISBN
978-1-4244-1705-6
Electronic_ISBN
978-1-4244-1706-3
Type
conf
DOI
10.1109/ICIT.2008.4608629
Filename
4608629
Link To Document