DocumentCode :
2714585
Title :
A simple repetitive controller embedded in PI-based UPS for reducing Total Harmonic Distortion with nonlinear loads
Author :
Haibing Hu ; Qingbo Hu ; Zhengyu Lu
Author_Institution :
Sch. of Electr. Eng., Zhejiang Univ., Hangzhou
fYear :
2006
fDate :
18-22 June 2006
Firstpage :
1
Lastpage :
5
Abstract :
This paper presents a simple plug-in repetitive control scheme for the PI-based UPS control to reduce periodic distortions caused by nonlinear loads. The drawback of the conventional PI-controlled UPS is presented under the rectifier-type nonlinear load conditions. A plug-in repetitive controller is adopted to address this problem. The analysis of the proposed control scheme reveals the repetitive controller could be very simple since the control plant is remodeled by multi-loop PI/P controllers. The effectiveness of the proposed scheme is verified in a 2 KW (50 Hz) prototype using a single chip digital signal processor (DSP) TMS320F2812. Experimental results show that the control scheme can both lower a THD below 3.4% under nonlinear loads and preserve good dynamic response
Keywords :
PI control; digital signal processing chips; dynamic response; harmonic distortion; uninterruptible power supplies; 2 kW; 50 Hz; DSP TMS320F2812; PI-based UPS control; THD; dynamic response; multiloop PI controllers; plug-in repetitive controller; rectifier-type nonlinear load conditions; single chip digital signal processor; total harmonic distortion; Control systems; Open loop systems; Pi control; Pulse width modulation; Pulse width modulation inverters; Sliding mode control; Three-term control; Total harmonic distortion; Uninterruptible power systems; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Electronics Specialists Conference, 2006. PESC '06. 37th IEEE
Conference_Location :
Jeju
ISSN :
0275-9306
Print_ISBN :
0-7803-9716-9
Type :
conf
DOI :
10.1109/PESC.2006.1712064
Filename :
1712064
Link To Document :
بازگشت