• DocumentCode
    271593
  • Title

    Moisture level content analysis in oil impregnated pressboard used in power transformers

  • Author

    Sebok, Milan ; Zukowski, Paweł ; Koltunowicz, Tomasz N. ; Kierczynski, Konrad ; Subocz, J. ; Szrot, Marek

  • Author_Institution
    Dept. of Meas. & Appl. Electr. Eng., Univ. of Zilina, Zilina, Slovakia
  • fYear
    2014
  • fDate
    19-20 May 2014
  • Firstpage
    369
  • Lastpage
    374
  • Abstract
    The article presents the results of research based on the DC electrical conductivity of wet paper depending on the moisture content and temperature of the samples. The change of moisture content does not change the activation energy of conductivity. The conductivity is performed by the hopping mechanism between the nearest possible holes which are formed in the material with nanodrops of water by the plotting of theoretical dependence that accurately describes the dependence of the conductivity of the water content and temperature. Medium size of nanodrops was about 1.5 nm, and the composition contains about 220 molecules of water.
  • Keywords
    electrical conductivity; impregnated insulation; moisture; power transformer insulation; transformer oil; water; DC electrical conductivity; hopping mechanism; moisture level content analysis; oil impregnated pressboard; power transformers; water content conductivity; water nanodrops; wet paper; Conductivity; Electrodes; Electronic ballasts; Humidity; Moisture; Nanostructured materials; DC conductivity; electrotechnic pressboard; jump exchange of electron; moisture content; potential well;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    ELEKTRO, 2014
  • Conference_Location
    Rajecke Teplice
  • Print_ISBN
    978-1-4799-3720-2
  • Type

    conf

  • DOI
    10.1109/ELEKTRO.2014.6848920
  • Filename
    6848920