Investigation of nuisance trips in microprocessor based transformer differential relay
Author :
Sutherland, Peter E.
Author_Institution :
GE Energy Services, Schenectady, NY, USA
fYear :
2010
fDate :
9-13 May 2010
Firstpage :
1
Lastpage :
8
Abstract :
A “nuisance trip” of a microprocessor based transformer differential relay was observed, with an unknown cause. The relay settings were modified with a higher pickup and an alarm at a more sensitive setting. The relay was then able to capture an event, which then did not cause tripping. The results were analyzed and found to be caused by energization of a downstream transformer. In addition, the CT ratio on the transformer primary was excessively high, which was corrected by auxiliary CTs. Based on these results, no further changes needed to be made to the relay settings.
Keywords :
Circuit faults; Control systems; Current transformers; Digital relays; Electronic equipment; Microprocessors; Power cables; Power system protection; Power system relaying; Protective relaying; Differential protection; digital relays; microprocessor relays; protective relays; transformer protection;