• DocumentCode
    2717472
  • Title

    Inclusion of the zero-sequence mutual impedance in a distributed parameter model of transmission lines

  • Author

    de Andrade, L. ; Sorrentino, E.

  • Author_Institution
    Fac. de Eng., Univ. do Porto, Porto, Portugal
  • fYear
    2010
  • fDate
    16-19 May 2010
  • Firstpage
    242
  • Lastpage
    245
  • Abstract
    This article presents a method for the inclusion of the zero-sequence mutual impedance in a distributed parameter model of transmission lines. An analytical deduction of the line constants was developed for the single-phase case of magnetically coupled circuits, and these constants were used in the line model with symmetrical components. The method was tested with the measurements from fault records. First, the phasors are computed from the recorded waveforms, and then the sequence components are calculated. The record from one line end is used to compute the theoretical values of the remote line end, and these computed values are compared with the record of the remote line end. The results without the effect of the zero-sequence mutual impedance are also computed in order to show the differences.
  • Keywords
    Circuit testing; Coupled mode analysis; Coupling circuits; Distributed parameter circuits; Impedance; Magnetic analysis; Magnetic circuits; Transmission line measurements; Transmission line theory; Transmission lines; distributed parameters; parallel transmission lines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Environment and Electrical Engineering (EEEIC), 2010 9th International Conference on
  • Conference_Location
    Prague, Czech Republic
  • Print_ISBN
    978-1-4244-5370-2
  • Electronic_ISBN
    978-1-4244-5371-9
  • Type

    conf

  • DOI
    10.1109/EEEIC.2010.5489983
  • Filename
    5489983