• DocumentCode
    2717777
  • Title

    Swept frequency response tests for condition monitoring of power transformers

  • Author

    Al-Khayat, Nazar ; Haydock, Lawrence ; McDowell, G.

  • Author_Institution
    Dansfoss Flowmetering Ltd., Gloucester, UK
  • fYear
    1995
  • fDate
    34729
  • Firstpage
    42552
  • Lastpage
    42556
  • Abstract
    In 1988, ERA Technology, in collaboration with The Nottingham Trent University, started a detailed program of research for the development of a means of monitoring the condition of a power transformer using the frequency response analysis technique. The research work concentrated on the establishment of a mathematical model of the transformer windings. The models developed were general and accurate. Overall 11 transformers were tested (500kVA - 70MVA). They range from distribution type, arc furnace, power station generator and neutral earthing reactors. In this paper, attention is centred on measuring and predicting the frequency response of iron cored disk-type windings in a 500 kVA distribution type transformer
  • Keywords
    distribution networks; frequency response; power transformer testing; transformer cores; transformer windings; 500 kVA to 70 MVA; condition monitoring; distribution type transformer; iron cored disk-type windings; mathematical model; power transformers; research; swept frequency response tests; transformer windings;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Condition Monitoring of Electrical Machines, IEE Colloquium on
  • Conference_Location
    London
  • Type

    conf

  • DOI
    10.1049/ic:19950102
  • Filename