• DocumentCode
    2721964
  • Title

    Development of external diagnosis for terminal in XLPE cables

  • Author

    Onoda, H. ; Morishita, Y. ; Watanabe, M. ; Nagayama, T. ; Suzuki, H. ; Abe, K.

  • Author_Institution
    Chubu Electr. Power Co., Inc., Nagoya, Japan
  • fYear
    2009
  • fDate
    26-30 Oct. 2009
  • Firstpage
    1
  • Lastpage
    5
  • Abstract
    To develop diagnostic method for terminals in aged XLPE cable lines, an external diagnosis of deterioration signals relating to partial discharge generated in the aged terminal has been investigated. The authors focused on acetylene as the particular gas produced by discharge from the results on partial discharge experiment using sheet specimens with a void. It was indicated from the results that gas analysis, aimed at detection of acetylene in the air in the metal casing of the terminal, had possibility to the applied to the external diagnosis. As result, based on the results of the correlation study between gas analysis results and dismantlement investigation of aged CV cable line terminals, it was determined that it is possible to use acetylene analysis as a deterioration diagnosis method for aged terminals.
  • Keywords
    XLPE insulation; chemical analysis; electric connectors; partial discharges; power cable insulation; power cable testing; acetylene detection; aged XLPE cable lines; aged terminal; cross linked polyethylene cables; deterioration diagnosis; gas analysis; partial discharge; Aging; Asia; Cables; Electrodes; Materials testing; Partial discharges; Petroleum; Rubber; Sheet materials; Silicon; Acetylene; External diagnosis; Gas analysis; Partial discharge; Terminal; XLPE cable;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission & Distribution Conference & Exposition: Asia and Pacific, 2009
  • Conference_Location
    Seoul
  • Print_ISBN
    978-1-4244-5230-9
  • Electronic_ISBN
    978-1-4244-5230-9
  • Type

    conf

  • DOI
    10.1109/TD-ASIA.2009.5357027
  • Filename
    5357027